Industrial Refrigeration — Temperature-Controlled Logistics Facility, West Africa

A centralized industrial refrigeration system with a closed-loop glycol network serving a temperature-controlled logistics facility.

Location
West Africa
Company
Fox Cooling2026
Discipline
Industrial Refrigeration & Hydraulic Engineering
My involvement
Team contributorSince February 2026

01Overview

Project overview

The facility is cooled by a centralized industrial refrigeration system. Chillers cool a closed glycol loop, which is pumped through a distribution network to industrial air coolers in the temperature-controlled spaces.

This case study describes the engineering topics involved in general terms. The system diagrams on this page are general engineering illustrations, not the project's design.

System
Centralized glycol refrigerationClosed loop
Served spaces
Temperature-controlled logisticsIndustrial air coolers

02My contribution

What I did on this project

I have been involved in this project since February 2026 as part of the Fox Cooling team, contributing to engineering and design development, technical evaluation, equipment selection and supplier coordination.

What I did myselfPerformed

  • Equipment comparisons
  • Manufacturer coordination
  • Technical clarifications
  • Datasheet reviews
  • Technical submittals
  • Design development support

Where I contributed to team workContributed

  • Refrigeration engineering
  • Hydraulic engineering
  • Expansion & pressurization
  • Water treatment & preservation

The system was engineered by a team. I did not independently design, approve, commission or manage the installation.

03System concept

How this type of system works

A general illustration of the engineering principles involved, not the project's design. Select a part to highlight it in the diagram.

General concept — not the project design
General concept of a closed-loop glycol system: a chiller plant with primary pumps is separated from the distribution circuit by a hydraulic decoupler; secondary duty/standby pumps with variable frequency drives deliver glycol to air coolers; air separation, vacuum degassing and expansion and pressurization equipment act on the return. Equipment quantities are not shown. This is not the design of any specific project. CLOSED-LOOP GLYCOL SYSTEM — GENERAL CONCEPT PRIMARY / SECONDARY PUMPING · EQUIPMENT QUANTITIES NOT SHOWN GLYCOL SUPPLY GLYCOL RETURN CHILLER PLANT ONE OR MORE UNITS PRIMARY PUMPS DUTY / STANDBY VFD SECONDARY PUMPS DUTY / STANDBY · VFD HYDRAULIC DECOUPLER PRIMARY / SECONDARY EXPANSION & PRESSURIZATION VACUUM DEGASSER AIR SEP. AIR COOLERS TEMPERATURE-CONTROLLED SPACES GENERAL ENGINEERING ILLUSTRATION — NOT A PROJECT DESIGN OR DRAWING
Figure 1 — General concept of a closed-loop glycol system with primary/secondary pumping: chiller plant, hydraulic decoupling, duty/standby secondary pumps with VFDs, air coolers, and pressure holding and gas removal on the return. It illustrates engineering principles only: it does not show the project's design, arrangement or equipment quantities.Swipe to see the whole diagram
  1. Production

    Chillers cool the glycol in the primary circuit, circulated by primary pumps.

  2. Hydraulic decoupling

    A hydraulic decoupler separates the primary (production) circuit from the secondary (distribution) circuit.

  3. Distribution

    Secondary pumps in duty/standby, with variable frequency drives, deliver glycol to the air coolers.

  4. Pressure holding & gas removal

    Expansion and pressurization equipment holds the system pressure; air separation and vacuum degassing remove gas.

04Engineering involvement

Areas of engineering involvement

The engineering areas I worked in on this project, marked by the kind of involvement.

  • PerformedWork I carried out myself
  • ContributedTeam work I contributed to

Technical coordination

Performed
  • Equipment comparisons
  • Manufacturer coordination
  • Technical clarifications
  • Datasheet reviews
  • Technical submittals
  • Design development support

Refrigeration engineering

Contributed
  • Centralized glycol refrigeration architecture
  • Cooling requirements
  • Operating temperatures
  • Chiller and air cooler integration

Hydraulic engineering

Contributed
  • Pump technical evaluation
  • Duty/standby configurations
  • Hydraulic distribution
  • VFD integration
  • Hydraulic decoupling

Expansion & pressurization

Contributed
  • Expansion vessels
  • Pressurization equipment
  • Vacuum degassing
  • Air separation

Water treatment & preservation

Contributed
  • Glycol corrosion protection
  • Corrosion-inhibitor evaluation
  • Material compatibility considerations
  • Wet preservation strategies

05Equipment

Equipment categories

Chillers

A chiller plant producing the glycol cooling.

Air coolers

Industrial air coolers in the temperature-controlled spaces.

Pumps & drives

Duty/standby pumping arrangements with variable frequency drives.

Hydraulic decoupling

Hydraulic decoupling between the primary (production) and secondary (distribution) circuits.

Expansion & pressurization

Expansion and pressurization equipment that holds the system pressure as the fluid volume changes with temperature.

Degassing & air separation

Vacuum degassing and air separation to keep the glycol loop free of gas.

06Engineering considerations

What makes these systems demanding

General engineering principles behind the work, without project figures.

  1. Low-temperature glycol operation

    At sub-zero glycol temperatures, fluid properties drive pump selection, heat-transfer performance and freeze protection.

  2. Closed-loop volume and pressure

    In a closed glycol loop the fluid volume changes with temperature and must be held within its pressure limits, which makes expansion, pressurization and gas removal central to the design.

  3. Pump sizing, diversity and part-load operation

    Pumps are sized on the hydraulic requirement of the system rather than the sum of the connected loads: diversity between loads, duty/standby redundancy and variable frequency drives for part-load operation all shape the selection.

  4. Wet preservation

    Glycol systems can stay filled before they enter service, so corrosion protection, inhibitor choice and material compatibility belong in the design stage, not only in commissioning.

  5. International coordination

    Equipment from several manufacturers had to be compared, clarified and coordinated for a project in West Africa.

08Experience gained

Engineering lessons from the project

  • Reading manufacturer datasheets against the actual operating point: glycol, temperature and duty, not catalogue conditions.
  • Seeing how expansion, pressurization and degassing work together as one system in a large closed loop.
  • Comparing pumps and redundancy arrangements on technical grounds as well as cost.
  • Taking wet preservation and water treatment into account at the design stage, not only at commissioning.

This case study presents a generalized engineering overview based on professional experience. Client identities, project-specific specifications, commercial information and proprietary system configurations have been omitted. All illustrations are conceptual and do not represent actual project drawings or installations.