Office sizing guide by cassette count — a preliminary rule of thumb, not an NF, IPC or IMC requirement. Check the unit's drain connection and the project spec.
Reverse slope check
Enter the run and the drop you have room for (e.g. space between false ceiling and slab).
Slope you get
–
Maximum run length
%
Tap ± to make a level negative.
Keep 5–10 cm clear of the limit.
Pipe can run up to
–
Total space–
Safety margin–
Usable drop–
Lowest pipe level–
Multi-segment run
Add sections in order, from the high end towards the drain. Enter the cassettes joining at the start of each section; the pipe size uses the running total.
Level at each joint
Total length–
Total drop–
Final level–
Paste into Excel or an AutoCAD table.
Units
Calculation method
Project design preferences (not code or ASHRAE requirements)
Colour bands used for every duct size shown. Green = below the first value, yellow = between the two values, red = above the second value. Saved with the project.
m/s
m/s
Pa/m
Pa/m
: 1
Inputs
L/s
m/s
Pa/m
mm
mm
mm
Ceiling space (optional)
Space between false ceiling and slab, minus clearances, gives the deepest duct that fits. Leave depth empty to use it automatically.
mm
mm
mm
Include hangers, insulation, sprinkler pipes or anything else that takes space.
m
ΣC = sum of fitting loss coefficients referenced to the duct velocity (for example from the ASHRAE Duct Fitting Database).
Rectangular duct
–
Based on ASHRAE Fundamentals duct friction method (Darcy–Weisbach with Colebrook–White since v0.1.3): galvanized steel duct (roughness 0.09 mm), standard air 1.204 kg/m³, Huebscher equivalent diameter for rectangular ducts. Width is rounded up to the next 50 mm / 2 in step (assumed standard step); velocity, friction and aspect ratio are recalculated for the selected size.
Water
°C
Flow
Flow from cooling / heating load (optional)
°C
Fills in the flow rate: flow = load ÷ (ρ · cp · ΔT).
Pipe
Use the inner diameter from the supplier's catalogue (depends on pressure class / SDR).
% of length
Extra equivalent length for elbows, tees and valves.
Design limits
Pa/m
m/s
m/s
Friction rate
–
Darcy–Weisbach with the Colebrook–White friction factor (64/Re when laminar). Water properties from an IAPWS-95 / IAPWS-2008 table (liquid water at 3 bar abs, 0–100 °C, interpolated every 5 °C). Steel roughness 0.045 mm; Sch 40 inner diameters per ASME B36.10M.
Cooling capacity
TR
kW
BTU/h
1 TR = 3.517 kW = 12,000 BTU/h
Airflow
CFM
m³/h
L/s
1 CFM = 1.699 m³/h = 0.472 L/s
Pressure
Pa
in. wg
bar
1 in. wg = 249.09 Pa · 1 bar = 100,000 Pa
Inches ↔ DN ↔ OD
Designed by Eng. Joe Saad Version 0.1.7 · formerly Pipe Slope & MEP Calculator